Low Voltage Duty Calculator
Compare available fault current and X/R with a breaker, fuse or switchgear rating. Calculates asymmetrical and peak capability, X/R multiplying factors, adjusted duty and pass/fail.
When to use this calculator
UL listed equipment typically carries a single interrupting or short-circuit rating in symmetrical RMS amperes. It is not always sufficient to only compare that rating to the calculated symmetrical fault current.
Ratings are given based on testing at a specific X/R ratio. The X/R ratio drives how much DC offset it carries in the first cycle, and subsequently how high its peak and asymmetrical RMS current rise. When the calculated X/R is higher than the test X/R, the peak or asymmetrical current that the equipment was tested to can be exceeded, even while the symmetrical current is below its rating.
For example, a 65kA breaker (test X/R=4.9) with 60kA (X/R=12) available passes on symmetrical current alone. Its first-cycle peak, however, is 150 kA against 140 kA tested. The breaker is overdutied.
IEEE C37.13 simplifies this process by calculating a multiplication factor that adjusts the calculated RMS symmetrical current to account for this. Therefore, the adjusted current can be directly compared to the published equipment rating.
Low Voltage Duty Calculator
Select whatever inputs are available and enter their values. The calculator automatically determines which additional parameters can be calculated.
Equations and calculation basis
First-cycle asymmetry
- Isym is the calculated ANSI symmetrical RMS fault current. X/R is the calculated X/R ratio of the fault.
- Both factors assume maximum DC offset, evaluated one half cycle after fault initiation (IEEE 3002.3 Eq. 66 and 67).
- Asymmetrical RMS factor and current
- Kasym(X/R) = √(1 + 2e−2π/(X/R))
Iasym = Isym × Kasym(X/R) - Peak factor and current
- Kpeak(X/R) = √2 × (1 + e−π/(X/R))
Ipeak = Isym × Kpeak(X/R) - X/R from asymmetrical RMS current
- X/R = −2π / ln[((Iasym / Isym)2 − 1) / 2]
Valid for 1 ≤ Iasym / Isym < √3 - X/R from peak current
- X/R = −π / ln[Ipeak / (√2 × Isym) − 1]
Valid for √2 ≤ Ipeak / Isym < 2√2
Equipment capability
Irated is the symmetrical RMS interrupting or withstand rating, demonstrated at the test X/R.
- Tested asymmetrical and peak capability
- Iasym,tested = Irated × Kasym(X/Rtest)
Ipeak,tested = Irated × Kpeak(X/Rtest) - Test power factor and X/R
- PFtest = 1 / √(1 + (X/Rtest)2)
X/Rtest = √(1 − PFtest2) / PFtest
Duty multiplication factors and pass/fail
The max[1, …] term ensures multiplication factor is never below 1. When the system X/R is at or below the test X/R, MF = 1.
- Asymmetrical RMS multiplying factor
- MFasym = max[1, Kasym(X/R) / Kasym(X/Rtest)]
= max[1, √((1 + 2e−2π/(X/R)) / (1 + 2e−2π/(X/Rtest)))] - Peak multiplying factor (C37.13 / SKM LVF)
- MFpeak = max[1, Kpeak(X/R) / Kpeak(X/Rtest)]
= max[1, (1 + e−π/(X/R)) / (1 + e−π/(X/Rtest))] - Adjusted symmetrical duty
- Iadj = Isym × MF
MF = MFpeak or MFasym, per the governing duty basis
Worst case: MF = max(MFpeak, MFasym) - Pass/fail
- ANSI comparison: pass when Irated ≥ Iadj
Direct comparisons, which give the same result:
Irated ≥ Isym, and
Peak basis: Ipeak,tested ≥ Ipeak
Asymmetrical RMS basis: Iasym,tested ≥ Iasym
Worst case: both of the above
Pass/fail should use the duty basis applicable to the equipment rating and test standard. Peak current relates to mechanical stress, asymmetrical RMS current relates to heating. SKM uses peak, ETAP defaults to asymmetrical RMS, while worst case is the most conservative.
Standard test X/R ratios
This table shows typical short-circuit test power factors from UL and ANSI equipment standards. The test X/R corresponds to the highest power factor permitted in each range. Kasym and Kpeak are the tested asymmetrical RMS and peak capabilities per unit of the symmetrical rating. Duty basis is the RMS symmetrical multiplication factor that gets applied to determine Pass/Fail.
| Equipment | Standard | Short-circuit rating | Test PF | Test X/R | Kasym | Kpeak | Duty basis |
|---|---|---|---|---|---|---|---|
| LV power circuit breaker, unfused | ANSI C37.13 / UL 1066 | All | 15% | 6.6 | 1.331 | 2.293 | Peak1 |
| LV metal-enclosed switchgear | ANSI C37.20.1 / UL 1558 | All | 15% | 6.6 | 1.331 | 2.293 | Peak1 |
| LV power circuit breaker, fused | ANSI C37.13 / UL 1066 | All | 20% | 4.9 | 1.247 | 2.159 | Asym RMS2 |
| Low-voltage fuse | UL 248 | All | ≤ 20% | 4.9 | 1.247 | 2.159 | Asym RMS3 |
| Molded and insulated case circuit breakers | UL 489 | ≤ 10 kA | 45–50% | 1.7 | 1.025 | 1.637 | Peak4 |
| 10–20 kA | 25–30% | 3.2 | 1.132 | 1.944 | |||
| > 20 kA | 15–20% | 4.9 | 1.247 | 2.159 | |||
| Panelboards, switchboards and motor control centers | UL 67 / UL 891 / UL 845 | ≤ 10 kA | 45–50% | 1.7 | 1.025 | 1.637 | Peak4 |
| 10–20 kA | 25–30% | 3.2 | 1.132 | 1.944 | |||
| > 20 kA | 15–20% | 4.9 | 1.247 | 2.159 | |||
| Transfer switches | UL 1008 | ≤ 10 kA | 40–50% | 1.7 | 1.025 | 1.637 | Peak4 |
| 10–20 kA | 25–30% | 3.2 | 1.132 | 1.944 | |||
| > 20 kA | ≤ 20% | 4.9 | 1.247 | 2.159 |
Use manufacturer's published test data if available.
Duty basis notes
- Peak basis. IEEE C37.13 (Table 3 multiplying factors) and IEEE 3002.3-2018 Eq. 67 rate unfused low-voltage power circuit breakers on first-cycle peak current. SKM software uses this methodology for equipment evaluation as can ETAP as an option.
- Asymmetrical RMS basis. IEEE 3002.3-2018 Eq. 66 gives the first-cycle asymmetrical RMS current and associates it with fused low-voltage power circuit breakers.
- Asymmetrical RMS basis, by extension of IEEE 3002.3 Eq. 66 to standalone fuses, which respond to asymmetrical RMS (heating) current. Not stated explicitly for UL 248 fuses. Confirm with the fuse manufacturer.
- Peak basis, common industry practice (e.g. using SKM or ETAP software) for UL 489 molded and insulated case breakers. Transfer switches and other assemblies are assumed to to use peak basis as well.
Evaluate your power system
Power System Calcs provides short circuit studies, protective device coordination studies, and arc flash studies for commercial, industrial, and mission-critical facilities.
Request a quote