Engineering Tools

Generator Parameter Calculator

Turn generator nameplate and manufacturer data into the parameters used for power system studies. Calculate full load amps, per-unit resistance, X/R ratios, and DC time constant.

What are generator parameters used for?

Generator parameters can be used to model generator characteristics on a time-current characteristic (TCC) plot and to calculate the generator's fault contribution for arc flash and equipment duty studies. Typical TCC elements:

  • Full load amps
  • Overload curve
  • Short-circuit withstand capability point
  • Short-circuit decrement curve

Generator Parameter Calculator

Enter the available generator manufacturer's published/nameplate data in boxes 1 and 2 to calculate the values to the right.

1. Generator rating

kVA, kW & power factor

Select Calculate for one value to be calculated from the other two. Leave all three unchecked to enter every value manually.

2. Impedance and reactance
Base kVA of the below reactance values.
Changing units clears the entry.
3. Additional manufacturer data

Optional inputs for reference only. No impact to calcuated values to the right.

Direct-axis short-circuit time constant.
Direct-axis short-circuit time constant.

Example based on: CAT 3.0 MW generator data sheet.

Formulas and calculation basis

Full load amps
FLA = rated kVA × 1,000 / (√3 × VLL)
Rating conversions
kW = kVA × PF
kVA = kW / PF
PF = kW / kVA
Base impedance
Zbase = VLL² / (base kVA × 1,000)
Per-unit stator resistance
For a Wye line-to-line entry: Ra (Ω/phase) = Ra (Ω L-L) / 2
Ra (pu) = Ra (Ω/phase) / Zbase
When Ra is entered in pu, it is used directly.
X/R ratios
x/r (subtransient) = X″d (pu) / Ra (pu)
x/r (neg sequence) = X2 (pu) / Ra (pu)
x/r (zero sequence) = X0 (pu) / Ra (pu)
DC time constant
Tdc (ms) = X″d (pu) / (2π × f × Ra (pu)) × 1,000

VLL is rated line-to-line voltage in volts, f is frequency in hertz. The base kVA is three-phase apparent power. Resistance and reactance must be on the same base. Changing the base kVA does not convert the entered reactances, use the published manufacturer's data.

X′d, Xd, Td″, and Td′ can be used to approximate the generator decrement. The Tdc result above describes DC decay using x/r (subtransient). This page calculates parameters, not overload or decrement curves, withstand limits, incident energy, or equipment duty.

Manufacturer data sheets specify the rating and voltage bases for per-unit reactances . See the CAT 3.0 MW generator data sheet used for the calculator example. Its 9.0E-4 Ω stator resistance is entered as 0.0009 Ω/phase for the SERIES STAR connection.

Evaluate your generator source contributions

Request a quote