Engineering Tools

Generator Parameter Calculator

Turn generator nameplate and manufacturer data into the parameters used for power system studies. Calculate full load amps, per-unit resistance, X/R ratios, and DC time constant.

What are generator parameters used for?

Generator parameters can be used to model generator characteristics on a time-current characteristic (TCC) plot and to calculate the generator's fault contribution for arc flash and equipment duty studies. Typical TCC elements:

  • Full load amps
  • Overload curve
  • Short-circuit withstand capability point
  • Short-circuit decrement curve

Generator Parameter Calculator

Enter the available generator manufacturer's published/nameplate data in boxes 1 and 2 to calculate the values to the right.

1. Generator rating

kVA, kW & power factor

Select Calculate for one value to be calculated from the other two. Leave all three unchecked to enter every value manually.

2. Impedance and reactance
Base kVA of the below reactance values.
Changing units clears the entry.
3. Additional manufacturer data

Optional. Td″, Td′, et, If and Ifg are used for the fault currents and decrement curve. Ambient and temperature rise are for reference only and do not affect calculated values.

Direct-axis short-circuit time constant.
Direct-axis short-circuit time constant.
Defaults to 1.0 pu. Leave If and Ifg blank to use no-load excitation.
Field current at no load, rated volts.
Field current at the prefault load.
4. Study base conversion

Optional. Converts the reactances and Ra to the base used in your system model.

For example, 10,000 kVA for a 10 MVA system base.
Leave blank to use the rated voltage.

Example based on: CAT 3.0 MW generator data sheet.

Formulas and calculation basis

Ratings and base values

Full load amps
FLA = rated kVA × 1,000 / (√3 × VLL)
Rating conversions
kW = kVA × PF
kVA = kW / PF
PF = kW / kVA
Base impedance
Zbase = VLL² / (base kVA × 1,000)
Base current
Ibase = base kVA × 1,000 / (√3 × VLL)
Ibase = FLA when the reactance base equals rated kVA.

Resistance, X/R and DC time constant

Per-unit stator resistance
For a Wye line-to-line entry: Ra (Ω/phase) = Ra (Ω L-L) / 2
Ra (pu) = Ra (Ω/phase) / Zbase
When Ra is entered in pu, it is used directly.
X/R ratios
x/r (subtransient) = X″d (pu) / Ra (pu)
x/r (neg sequence) = X2 (pu) / Ra (pu)
x/r (zero sequence) = X0 (pu) / Ra (pu)
DC time constant
Tdc (ms) = X″d (pu) / (2π × f × Ra (pu)) × 1,000

The zero-sequence x/r is approximate. It divides X0 by the positive-sequence stator resistance because the zero-sequence resistance R0 is rarely published and usually differs from Ra.

Fault currents

Three-phase bolted fault
I″k = et × Ibase / X″d
I′k = et × Ibase / X′d
Ik = Ibase × id
Steady-state component
id = (et / Xd) × (If / Ifg)
If / Ifg = 1 when either field current is blank.
Line-to-ground bolted fault
ILG = 3 × et × Ibase / (X″d + X2 + X0)
Solidly grounded wye only.
Peak asymmetrical current
Ipeak = √2 × I″k × (1 + e−π / (X/R))
X/R is the subtransient x/r.

Fault currents assume a bolted fault at the generator terminals with prefault terminal voltage et. If is the regulator field current at the prefault load and Ifg is the field current at no-load rated voltage, so loading the generator before the fault raises the steady-state current. Resistance is neglected in the current magnitudes. Resistance- or impedance-grounded neutrals limit line-to-ground current to a value set by the grounding device.

Decrement curve

Symmetrical rms current
Iac(t) = Ibase × [(et/X″d − et/X′d)e−t/Td″ + (et/X′d − id)e−t/Td′ + id]
id = (et / Xd) × (If / Ifg)
Total asymmetrical rms current
Idc(t) = √2 × I″k × e−t/Tdc
Itotal(t) = √(Iac(t)² + Idc(t)²)

Study base conversion

Change of base
Znew (pu) = Zold (pu) × (kVAnew / kVAold) × (Vold / Vnew)²

kVAold is the reactance base from box 2 and Vold is the rated voltage. X/R ratios and Tdc do not change with base.

VLL is rated line-to-line voltage in volts, f is frequency in hertz. The base kVA is three-phase apparent power. Resistance and reactance must be on the same base. Changing the reactance base kVA does not convert the entered reactances, so enter the manufacturer's published values on their stated base. Use the study base conversion to express them on your system base.

This page calculates parameters, fault currents and a constant-excitation decrement estimate. It does not calculate overload curves, withstand limits, incident energy, or equipment duty.

Manufacturer data sheets specify the rating and voltage bases for per-unit reactances. See the CAT 3.0 MW generator data sheet used for the calculator example. Its 9.0E-4 Ω stator resistance is entered as 0.0009 Ω/phase for the SERIES STAR connection.

Evaluate your generator source contributions

Request a quote