Generator Parameter Calculator
Turn generator nameplate and manufacturer data into the parameters used for power system studies. Calculate full load amps, per-unit resistance, X/R ratios, and DC time constant.
What are generator parameters used for?
Generator parameters can be used to model generator characteristics on a time-current characteristic (TCC) plot and to calculate the generator's fault contribution for arc flash and equipment duty studies. Typical TCC elements:
- Full load amps
- Overload curve
- Short-circuit withstand capability point
- Short-circuit decrement curve
Generator Parameter Calculator
Enter the available generator manufacturer's published/nameplate data in boxes 1 and 2 to calculate the values to the right.
Formulas and calculation basis
Ratings and base values
- Full load amps
- FLA = rated kVA × 1,000 / (√3 × VLL)
- Rating conversions
- kW = kVA × PF
kVA = kW / PF
PF = kW / kVA - Base impedance
- Zbase = VLL² / (base kVA × 1,000)
- Base current
- Ibase = base kVA × 1,000 / (√3 × VLL)
Ibase = FLA when the reactance base equals rated kVA.
Resistance, X/R and DC time constant
- Per-unit stator resistance
- For a Wye line-to-line entry: Ra (Ω/phase) = Ra (Ω L-L) / 2
Ra (pu) = Ra (Ω/phase) / Zbase
When Ra is entered in pu, it is used directly. - X/R ratios
- x/r (subtransient) = X″d (pu) / Ra (pu)
x/r (neg sequence) = X2 (pu) / Ra (pu)
x/r (zero sequence) = X0 (pu) / Ra (pu) - DC time constant
- Tdc (ms) = X″d (pu) / (2π × f × Ra (pu)) × 1,000
The zero-sequence x/r is approximate. It divides X0 by the positive-sequence stator resistance because the zero-sequence resistance R0 is rarely published and usually differs from Ra.
Fault currents
- Three-phase bolted fault
- I″k = et × Ibase / X″d
I′k = et × Ibase / X′d
Ik = Ibase × id - Steady-state component
- id = (et / Xd) × (If / Ifg)
If / Ifg = 1 when either field current is blank. - Line-to-ground bolted fault
- ILG = 3 × et × Ibase / (X″d + X2 + X0)
Solidly grounded wye only. - Peak asymmetrical current
- Ipeak = √2 × I″k × (1 + e−π / (X/R))
X/R is the subtransient x/r.
Fault currents assume a bolted fault at the generator terminals with prefault terminal voltage et. If is the regulator field current at the prefault load and Ifg is the field current at no-load rated voltage, so loading the generator before the fault raises the steady-state current. Resistance is neglected in the current magnitudes. Resistance- or impedance-grounded neutrals limit line-to-ground current to a value set by the grounding device.
Decrement curve
- Symmetrical rms current
- Iac(t) = Ibase × [(et/X″d − et/X′d)e−t/Td″ + (et/X′d − id)e−t/Td′ + id]
id = (et / Xd) × (If / Ifg) - Total asymmetrical rms current
- Idc(t) = √2 × I″k × e−t/Tdc
Itotal(t) = √(Iac(t)² + Idc(t)²)
Study base conversion
- Change of base
- Znew (pu) = Zold (pu) × (kVAnew / kVAold) × (Vold / Vnew)²
kVAold is the reactance base from box 2 and Vold is the rated voltage. X/R ratios and Tdc do not change with base.
VLL is rated line-to-line voltage in volts, f is frequency in hertz. The base kVA is three-phase apparent power. Resistance and reactance must be on the same base. Changing the reactance base kVA does not convert the entered reactances, so enter the manufacturer's published values on their stated base. Use the study base conversion to express them on your system base.
This page calculates parameters, fault currents and a constant-excitation decrement estimate. It does not calculate overload curves, withstand limits, incident energy, or equipment duty.
Manufacturer data sheets specify the rating and voltage bases for per-unit reactances. See the CAT 3.0 MW generator data sheet used for the calculator example. Its 9.0E-4 Ω stator resistance is entered as 0.0009 Ω/phase for the SERIES STAR connection.
Evaluate your generator source contributions
Power System Calcs provides short circuit studies, protective device coordination studies, and arc flash studies for commercial, industrial, and mission-critical facilities.
Request a quote