Engineering Tools

Arc Flash Calculator

Calculate arcing current, incident energy and arc flash boundary with IEEE 1584-2018 from 208 V to 15 kV, and the Lee method above 15 kV. Find the distance for a target incident energy, or the worst-case boundary for a known incident energy.

When to use this calculator

Incident energy is the thermal energy (heat) that a worker could be exposed to during an arc flash at the working distance. The arc flash boundary is the distance at which the incident energy falls to 1.2 cal/cm², the threshold of a second-degree burn. IEEE 1584-2018 provides methodology to calculate both values from the system voltage, bolted fault current, arcing duration, electrode configuration, conductor gap and enclosure size.

Each calculation is run twice: at the full arcing current, and at a reduced arcing current that allows for the variation in arcing current. A lower current can take a protective device longer to clear, so the reduced case can produce the higher incident energy. Clearing time is based on the response of the upstream protective device(s).

Use the worst-case boundaries option to calculate worst case arc flash boundaries for known incident energy values (such as PPE ratings) for any electrode configuration.

This calculator is a quick check for a single fault location. An arc flash study models the full system, including utility, generator and motor contributions, protective device settings and each operating scenario.

Arc Flash Calculator

Choose a calculation, then enter the system and equipment data. Results update as you type.

Calculation

Arcing current, incident energy and arc flash boundary for one piece of equipment.

1. System

208 V to 15 kV uses IEEE 1584-2018. The Lee method is utilized for voltages above 15 kV.

2. Equipment
Uses IEEE 1584-2018 typical gap, working distance and enclosure size. Choose Custom to edit them.

Enclosure size

Height and width under 20" count as 20", and stop affecting the result above 49". Below 600 V, an enclosure under 20" high and wide and 8" deep or less is shallow and uses its actual size.
3. Electrode configuration

Open-air configurations do not use the enclosure size.

4. Arcing duration

Clearing time can be determined from the calculated arcing fault current and the protective device's time-current characteristic curve.

Protective device clearing time. Cycles are at 60 Hz.
Optional. Leave blank to use the same arcing duration.
5. Target incident energy (optional)
Finds the distance at which incident energy falls to this value, for example the arc rating of available PPE.

Example: IEEE 1584-2018 Annex D.2, 480 V switchgear with 45kA available and a 61.3ms arcing duration (319ms at the reduced arcing current).

Equations and calculation basis

Methods and model range

IEEE 1584-2018 applies to three-phase AC equipment within the ranges below. Inputs outside them are still calculated, with a warning, since the equations are then extrapolated. For voltages above above 15 kV, the calculator uses the Lee method, which assumes the arcing current equals the bolted fault current and is generally very conservative.

Parameter208 V to 600 V601 V to 15 kVAbove 15 kV
MethodIEEE 1584-2018 equations for 600 V and belowIEEE 1584-2018, interpolated between 600 V, 2.7 kV and 14.3 kVLee method
Bolted fault current500A to 106kA200A to 65kAAny
Conductor gap6.35 mm to 76.2 mm19.05 mm to 254 mmNot used
Working distance12 in (305 mm) or more12 in (305 mm) or moreAny
Electrode configurationVCB, VCBB, HCB, VOA, HOAVCB, VCBB, HCB, VOA, HOANot used
EnclosureWidth at least 4 × gap. Height and width above 49 in (1244.6 mm) are treated as 49 in.Not used

Typical equipment values

IEEE 1584-2018 typical bus gaps, enclosure sizes and working distances. Shallow and deep enclosures are entered as 8" and 12" deep, since only whether the depth is 8" or less matters. Use the actual equipment data when available.

EquipmentGapEnclosure (H × W × D)Working distance
15 kV switchgear152 mm45 × 30 × 30 in36 in
15 kV MCC152 mm36 × 36 × 36 in36 in
5 kV switchgear104 mm36 × 36 × 36 in or 45 × 30 × 30 in36 in
5 kV MCC104 mm26 × 26 × 26 in36 in
Low-voltage switchgear32 mm20 × 20 × 20 in24 in
Low-voltage MCCs and panelboards25 mm14 × 12 × ≤ 8 in (shallow) or > 8 in18 in
Cable junction box13 mm14 × 12 × ≤ 8 in (shallow) or > 8 in18 in

Arcing current

  • Voc is the open-circuit (system) voltage in kV, Ibf the bolted fault current in kA and G the gap in mm.
  • Coefficients k1 to k10 depend on the electrode configuration and are given at 600 V, 2.7 kV and 14.3 kV (IEEE 1584-2018 Table 1).
Intermediate arcing current (Eq. 1)
Iarc,Voc = 10(k1 + k2 lg Ibf + k3 lg G) × (k4Ibf6 + k5Ibf5 + k6Ibf4 + k7Ibf3 + k8Ibf2 + k9Ibf + k10)
for Voc = 600 V, 2.7 kV and 14.3 kV
Final arcing current, 600 V and below (Eq. 25)
Iarc = 1 / √[(0.6/Voc)2 × (1/Iarc,6002 − (0.62 − Voc2) / (0.62 × Ibf2))]
Final arcing current, above 600 V (Eq. 16 to 18)
I1 = (Iarc,2700 − Iarc,600) / 2.1 × (Voc − 2.7) + Iarc,2700
I2 = (Iarc,14300 − Iarc,2700) / 11.6 × (Voc − 14.3) + Iarc,14300
I3 = I1(2.7 − Voc) / 2.1 + I2(Voc − 0.6) / 2.1
Iarc = I3 up to 2.7 kV, I2 above
Reduced arcing current (Eq. 2)
VarCf = k1Voc6 + k2Voc5 + k3Voc4 + k4Voc3 + k5Voc2 + k6Voc + k7 (Table 2)
Iarc,min = Iarc × (1 − 0.5 × VarCf)
Above 600 V, each intermediate arcing current is reduced before interpolation
Reduced arcing current, percent below Iarc (0.5 × VarCf)
VoltageVCBVCBBHCBVOAHOA
208 V13.85%14.43%15.70%14.55%15.72%
240 V13.66%14.10%15.47%14.23%15.49%
480 V12.33%11.84%13.80%11.99%13.85%
600 V11.70%10.85%13.02%11.00%13.10%
1 kV9.82%8.11%10.73%8.24%10.86%
4.16 kV2.34%2.16%2.64%1.84%3.45%
13.8 kV1.20%1.89%1.16%1.65%3.21%
15 kV1.08%2.14%1.17%1.86%3.24%

Enclosure size correction factor

Applies to VCB, VCBB and HCB. Open-air configurations use CF = 1. Dimensions are in mm unless noted.

Enclosure type
Shallow when Voc < 600 V, height and width < 508 mm (20 in) and depth ≤ 203.2 mm (8 in)
Typical otherwise
Equivalent width and height in inches (Table 6, Eq. 11 and 12)
Below 508 mm: 20 in (typical) or 0.03937 × d (shallow)
508 to 660.4 mm: 0.03937 × d
660.4 to 1244.6 mm: [660.4 + (d − 660.4)(Voc + A) / B] / 25.4
Above 1244.6 mm: as at 1244.6 mm
VCB height above 660.4 mm: 0.03937 × d, at most 49 in
Equivalent enclosure size (Eq. 13)
EES = (H1 + W1) / 2
A, B = 4, 20 (VCB); 10, 24 (VCBB); 10, 22 (HCB)
Correction factor (Eq. 14 and 15)
Typical: CF = b1EES2 + b2EES + b3
Shallow: CF = 1 / (b1EES2 + b2EES + b3) (Table 7)

Incident energy and arc flash boundary

  • T is the arcing duration in ms and D the distance in mm. Coefficients k1 to k13 are given at 600 V, 2.7 kV and 14.3 kV (Tables 3 to 5). k12 is the distance exponent.
  • At 600 V and below, the k3 term uses Iarc,600 and the k13 term the final Iarc, even for the reduced arcing current. For above 600 V, both use the intermediate arcing current at each voltage.
Incident energy (Eq. 3 to 6)
E = 12.552/50 × T × 10X + k12 lg D J/cm2
X = k1 + k2 lg G + k3Iarc / (k4Ibf7 + k5Ibf6 + … + k10Ibf) + k11 lg Ibf + k13 lg Iarc + lg(1/CF)
E (cal/cm2) = E (J/cm2) / 4.184 = 0.06 × T × 10X + k12 lg D
Arc flash boundary (Eq. 7 to 10)
AFB = 10[X − lg(20/T)] / (−k12) mm
20/T is the incident energy term at 1.2 cal/cm2
Distance for a target incident energy
Dtarget = 10[X − lg(Etarget / (0.06 T))] / (−k12) mm
Etarget in cal/cm2; at 1.2 cal/cm2 this is the arc flash boundary
Above 600 V (Eq. 19 to 24)
E, AFB and Dtarget are calculated at 600 V, 2.7 kV and 14.3 kV, then interpolated to Voc with the same equations as the arcing current

Each case uses its own arcing current and arcing duration. The case with the larger incident energy at the working distance governs, and its arc flash boundary is reported.

Lee method (above 15 kV)

V in kV, Ibf in kA, t in seconds and D in mm. The arcing current is taken as the bolted fault current, and the gap, electrode configuration and enclosure are not used.

Incident energy
E = 2.142 × 106 × V × Ibf × t / D2 J/cm2
Arc flash boundary and target distance
AFB = √(2.142 × 106 × V × Ibf × t / EB) mm
EB = 1.2 cal/cm2 (5.02 J/cm2), or the target incident energy

Worst-case boundary from a known incident energy

With the incident energy ED known at working distance D, everything in X cancels at 600 V and below, so the boundary depends only on the distance exponent. A smaller exponent means energy falls off more slowly with distance, giving a larger boundary.

600 V and below
AFB = D × (ED / 1.2)1 / −k12
VCB and VOA share the smallest exponent, 1.598 which leads to the governing worst case
Above 600 V
E is interpolated from three distance exponents, and supsequently also depends on bolted fault current. The calculator searches bolted fault currents from 200A to 65kA (the IEEE 1584-2018 model range) and arcing durations up to 2s, using both the full and reduced arcing currents, and reports the largest boundary. It uses the smallest typical enclosure, since that enclosure produces the known incident energy in the shortest arcing duration, which keeps the most cases within the 2s limit.
Distance exponent −k12 (IEEE 1584-2018 Tables 3 to 5)
Configuration600 V2.7 kV14.3 kV
VCB1.5981.5691.568
VCBB1.8091.7421.677
HCB2.0301.7231.655
VOA1.5981.5151.534
HOA1.9901.6391.633
Lee method
AFB = D × (ED / 1.2)1/2
IEEE 1584-2018 gives no typical working distances above 15 kV. Therefore, the typical working distance of 36" for 15 kV equipment is utilized. Custom working distances can be applied as well.